When a dry standpipe is required for a residential structure, it shall be designed and installed in accordance with the following:

A. Hydraulically designed to provide a minimum of 750 gpm at 250 psi.

B. The standpipe shall be designed by a Washington State Level 3 license holder or a PE.

C. In a location approved by Fire Prevention and the local fire district.

D. A 5-inch Storz Fire Department Connection on the supply side and a roof top connection (3 each, 2 1/2-inch gated with cap) on the discharge.

E. Locking caps required on the supply side.

(Ord. 2021-46s § 1, 2021)