A. Fire Department Connections. Fire Department Connections shall be installed in an approved location with the following considerations:

1. Within 25 feet of a fire hydrant.

2. On the same side of the emergency vehicle access as the hydrant.

3. Not in a collapse zone.

4. Locking caps required.

5. Minimum of 50 feet from structure.

6. Clustered when possible.

(Ord. 2021-46s § 1, 2021)