Skip to main content
Loading…
This section is included in your selections.

Sections 507.3 and 507.5.1 of the International Fire Code are deleted in their entirety and replaced with the following:

A. Scope. This Section addresses fire flow requirements for all buildings, portions of buildings, and facilities hereafter constructed. The requirements of this Section shall supersede any conditions, notes, or requirements on any plat when the Fire Marshal finds it creates a serious threat to the public health, safety, or welfare. Nothing in this Section shall be deemed to reduce, replace or waive any water system requirements in PCC 17C.60.165 or any other Pierce County Code.

B. Fire Flow Standards.

1. Water mains supplying fire flow shall maintain a minimum residual pressure of not less than 20 pounds per square inch (PSI) automatically.

2. A Certificate of Water Availability and water system vicinity map that is signed by the water purveyor shall be submitted at the time of building permit application for all newly constructed or modified buildings located within a water district.

3. The fire-flow calculation area shall be the total floor area of all floor levels within the exterior walls and under the combustible horizontal projections of the roof of a building with consideration to the following:

a. Buildings with Type IA and IB construction shall use the area of the three largest successive floors.

b. Open parking garages shall be determined by the area of the largest floor.

c. Any building constructed in the IRC located within 10 feet of another building on the same lot shall be considered as one fire flow calculation area unless separated by a fire-rated assembly.

d. Any building constructed in the IBC located within 20 feet of another building on the same lot shall be considered as one fire flow calculation area unless separated by a fire-rated assembly.

e. Each portion of a building separated by one or more fire-rated assemblies are considered as separate fire flow calculation areas.

f. Fire-rated assemblies are not permitted to reduce the fire flow calculation area within single-family residential dwellings.

Exception. Fire-rated assemblies are permitted to "separate" an attached garage from a residence and reduce by compartmentalization, the fire area of accessory buildings.

C. Fire Flow Requirements for Facilities. Facilities shall be provided with a minimum of 1,500 GPM for two hours. The requirement may be modified by the Fire Marshal per the International Fire Code, Appendix B.103.

D. Fire Flow Requirements for Buildings. Fire flow shall be automatically available and supplied at a residual pressure of not less than 20 PSI.

1. Residential Buildings.

a. Dwellings and Accessory Structures with Habitable Space. The fire flow requirements for dwellings and accessory structures with habitable space shall be as follows:

(1) Fire flow calculation area of less than 3,600 square feet shall be 750 GPM for 45 minutes;

(2) Fire flow calculation area of 3,600 square feet or more shall be 1,000 GPM for one hour.

(3) For replacement of manufactured and mobile homes in a park, fire flow is not required if all of the following are met:

(a) The home has a Class A or B roof; and

(b) Has a 10-foot clearance between the home and any adjacent home.

b. Accessory Structures.

(1) The fire flow requirements for accessory structures greater than 3,600 square feet shall be 750 GPM for 45 minutes.

(2) Exceptions to fire flow requirements:

(a) Buildings set back from all side and rear property lines of at least 20 feet and a minimum of 30 feet from other buildings on the same lot.

c. Agricultural Buildings.

(1) The fire flow requirements for agricultural buildings greater than 3,600 square feet (Group U) shall be 750 GPM for 45 minutes;

(2) Exception to fire flow requirements:

(a) The structure is set back from the side and rear lot lines of at least 30 feet and is at least 30 feet from other buildings on the same lot.

2. Buildings Constructed in the International Building Code and All Townhomes and Accessory Structures 3,600 Square Feet or Greater. The fire flow and duration requirements shall be as specified in Table 17C.60-3. Reductions to the required fire flow are permitted for an approved fire sprinkler system as follows:

a. Sprinkler Reductions.

(1) Installation of an NFPA 13 fire sprinkler system reduces the fire flow requirement by 75 percent, except for H occupancies which are reduced by 50 percent.

(2) Installation of an NFPA 13R fire sprinkler system reduces the fire flow requirement by 50 percent.

(3) Installation of an NFPA 13D fire sprinkler system reduces the fire flow requirement by 25 percent.

E. Exceptions to Fire Flow. The following exceptions apply to fire flow requirements for new buildings:

1. Fire protection credits as described in Table 17C.60-5 may be used in lieu of providing fire flow.

2. When at least 750 GPM for a duration of 45 minutes is available from an approved fire hydrant, it shall be credited toward the required fire flow. The additional fire flow requirement may be provided by using fire protection credits as described in Table 17C.60-5.

F. Exemptions from Fire Flow Requirements.

1. Buildings that are 600 square feet or less, located a minimum of 10 feet from property lines and 20 feet from structures, and not classified as Occupancy Group R, H, or I.

2. Storage structures that are used for the sole purpose of storing mineral products such as salt, sand, and/or rock, for road maintenance, or similar purposes that meet all of the following criteria:

a. Parking of motor vehicles in the storage shed shall be prohibited.

b. The storage of flammable or combustible materials in the storage shed shall be prohibited.

c. The roof covering shall be of Class A or B fire-resistant roofing material or meet NFPA 701.

d. Located a minimum of 20 feet from other structures.

3. Play sheds associated with schools and/or churches that meet all of the following criteria:

a. Do not require an automatic sprinkler system based on International Building Code requirements.

b. There shall be no restrictions to egress, i.e., benches, rails, walls, etc.

c. There shall be no interior walls or partitions within the roof line.

d. The roof covering shall be of Class A or B fire-resistant roofing material.

e. Located a minimum of 20 feet from other structures.

4. Picnic shelters that are 2,500 square feet or less and meet all of the following criteria:

a. Do not require an automatic sprinkler system based on International Building Code requirements.

b. All cooking within the picnic shelter shall be done within approved devices provided for that purpose.

c. There shall be no open burning within a picnic shelter except within an approved appliance or fireplace provided for that purpose.

d. There shall be a minimum of one exit on each side of the picnic shelter.

e. The roof covering shall be of Class A or B fire-resistant roofing material.

f. Located a minimum of 20 feet from other structures.

5. Vehicle covers/carports that meet all of the following criteria:

a. The vehicle cover shall be associated with a residential use.

b. The vehicle cover shall be located a minimum of three feet from property lines.

c. The vehicle cover shall be open on three sides.

6. Commercial buildings less than 3,600 square feet that meet all of the following criteria:

a. The fire area building is less than 3,600 square feet.

b. The property is located in a rural zone.

c. An NFPA 72 monitored fire alarm is installed in the building.

d. Thirty-foot minimum setbacks to all property lines and buildings on the same property.

e. Located within a fire district.

f. Not classified as an E, A, H, I, or R occupancy.

G. Hydrants. These standards shall apply to all new hydrant installations and when existing hydrants are replaced.

1. The location of hydrants shall be determined by the Fire Marshal, guided by the following:

a. The average spacing between fire hydrants for construction using the IBC and all townhomes shall not exceed that listed on Table 17C.60-4. Regardless of the average hydrant spacing, no portion of a building shall be farther from a hydrant than that distance listed in the last (far right) column of Table 17C.60-4. Distances shall be measured along approved EV Accesses and adjacent public and private roads and shared access facilities.

b. For residential buildings, the distance from the center point of lot frontage to a hydrant shall not exceed 350 feet, except as provided for in subsection G.1.c below.

c. Hydrants are not required on dead-end streets or shared access facilities not exceeding 600 feet in length and serving only residential buildings if there is an approved hydrant at the intersection.

d. Hydrants shall be provided along approved EV Accesses and adjacent public and private roads and shared access facilities. When practical, hydrants shall be located at street intersections. See Table 17C.60-4.

e. All new and existing approved public hydrants shall be considered available if accessible to the fire department by public or private roads, or shared access facilities, or approved on-site EV Accesses.

2. Exceptions to Hydrant Requirements. When hydrants cannot be installed in conformance with these standards due to topography, non-negotiable grades, or other similar conditions, the Fire Marshal may confer with the local Fire Chief, and may allow exceptions to these standards by requiring additional fire protection as specified in the most current edition of the International Fire Code adopted by the County.

3. Hydrant Valve Openings. Standard hydrants shall have not less than 5-inch main valve openings (MVO) with two 2 1/2 inch National Hose (N.H.) outlet ports and one 4 1/2 inch N.H. outlet port. All 4 1/2 inch outlet ports shall have 5-inch storz fittings. Hydrants shall meet current American Water Works Association (A.W.W.A.) Standards.

4. System Design for Automatic Operation. Water distribution systems supplying water for fire flow to fire hydrants shall be designed to maintain the designed and/or required water volume automatically.

TABLE 17C.60-3

Required Fire Flow for All Buildings Constructed Using the International Building Code, All Townhomes, and Accessory Structures Over 5,000 Square Feet

Construction Type in Accordance with the IBC

DURATION (HOURS)

REQUIRED FIRE FLOW (GPM)

IA and IB

IIA and IIIA

IV-H.T. VA

IIB IIIB

VB

WHEN TOTAL FIRE FLOW CALCULATION AREA IN SQUARE FEET IS EQUAL TO OR LESS THAN THESE VALUES

2

1,500

500

500

500

500

500

2

1,500

5,500

3,700

2,600

2,100

1,600

2

1,500

11,100

6,800

4,700

3,500

2,400

2

1,500

15,900

9,300

6,200

4,500

2,900

2

1,500

22,700

12,700

8,200

5,900

3,600

2

1,750

30,200

17,000

10,900

7,900

4,800

2

2,000

38,700

21,800

12,900

9,800

6,200

2

2,250

48,300

24,200

17,400

12,600

7,700

2

2,500

59,000

33,200

21,300

15,400

9,400

2

2,750

70,900

39,700

25,500

18,400

11,300

3

3,000

83,700

47,100

30,100

21,800

13,400

3

3,250

97,700

54,900

35,200

25,900

15,600

3

3,500

112,700

63,400

40,600

29,300

18,000

3

3,750

128,700

72,400

46,400

33,500

20,600

4

4,000

145,900

82,100

52,500

37,900

23,300

4

4,250

164,200

92,400

59,100

42,700

26,300

4

4,500

184,400

103,100

66,000

47,700

29,300

4

4,750

203,700

114,600

73,300

53,000

32,600

4

5,000

225,200

126,700

81,100

58,600

36,000

4

5,250

247,700

139,400

89,200

65,400

39,600

4

5,500

271,200

152,600

97,700

70,600

43,400

4

5,750

295,900

166,500

106,500

77,000

47,400

4

6,000

GREATER

GREATER

115,800

83,700

51,500

4

6,250

125,500

90,600

55,700

4

6,500

135,500

97,900

60,200

4

6,750

145,800

106,800

64,800

4

7,000

156,700

113,200

69,600

4

7,250

167,900

121,300

74,600

4

7,500

179,400

129,600

79,800

4

7,750

191,400

138,300

85,100

4

8,000

GREATER

GREATER

GREATER

 

TABLE 17C.60-4

Number and Distribution of Hydrants

Minimum Fire Flow Requirement (GPM)

Minimum # Of Hydrants

Average Spacing Between Hydrants (FT (1))

Maximum Distance From Hydrant to Any Portion of Building (FT)

500 – 1250

1

700

350

1500 – 1750

2

500

250

2000 – 2250

2

450

225

2500 – 2750

3

450

225

3000 – 3250

3

400

225

3500 – 4250

4

350

210

4500 – 5250

5

300

180

5500 – 5750

6

300

180

6000 – 6250

6

250

150

6500 – 7250

7

250

150

7500 or more

8 or more (2)

200

120

(1)    Where streets are provided with median dividers or where arterial streets are provided with four or more traffic lanes and have a traffic count of more than 30,000 vehicles per day, hydrant spacing shall comply with Table 17C.60-8 on both sides of the street.

(2)    One hydrant for each 1000 GPM or fraction thereof.

 

TABLE 17C.60-5

Residential Fire Protection Credits 

Options to Reduce Fire Flow (1)

% of Reduction

NFPA 13 D sprinkler system

(Required for structures 5,000 sq. ft. and greater)

100%

Building less than 2,000 sq. ft. or

-45%

Building less than 3,600 sq. ft.

-25%

Building less than 3,600 sq. ft. and minimum 50' setbacks to side and rear property lines

-5%

Accessory or Agricultural Structure Less than 3,600 sq. ft. without habitable space

-40%

Accessory or Agricultural Structure less than 3,600 sq. ft. without walls

-35%

30' setback to sides and rear property lines or

-20%

20' setback to sides and rear property lines

-15%

Fire-Rated Wallboard Throughout Interior

-20%

Class A or B roof

Metal Roof

-20%

30%

Exterior Siding Materials with a Class A or B Fire Rating

30%

Approved Kitchen Hood Suppression System

-25%

Monitored Residential Fire Alarm System

-25%

Existing Hydrant Credits:

Structures less than 3,600 sq. ft.

750 GPM/45 Min. Located 0-350'

100%

750 GPM/45 Min. Located 351'-500'

75%

Structures 3,600 sq. ft or Greater

1,000 GPM/60 Min. Located 0-350'

100%

750 GPM/45 Min. Located 0-350'

75%

1,000 GPM/60 Min. Located 351'-500'

75%

750 GPM/45 Min. Located 351'-500'

50%

Fire hydrants used for fire flow credits must be on the same side of the street that the building is on.

 

(Ord. 2024-528 § 1, 2024; Ord. 2021-46s § 1, 2021; Ord. 2016-85s § 1 (part), 2016; Ord. 2008-107 § 2 (part), 2008; Ord. 2004-30s § 4 (part), 2004)